Series 3000 - Battery Calculation
Print This Page
Series 3000 Battery Calculation
Line # System Components Quantity Stand-By
Current
(mA)
Maximum
Alarm
Current(mA)
Total
Stand-By
Current(mA)
Total
Alarm
Current(mA)
1 3000-6400 System Board (CP3, LPD, PSC, 1 ACM)
2 3000-6855 Addressable Communication Module (ACM)
3 2918 Zone Relay Module (ZRM)
Serial Devices
4 3000-6825 City Box Module (CBM)
5 2996 Networked Digital Communicator (NDC)
6 3000-6807 Remote Display Annunciator (RDA)
7 4010 Remote Annunciator (RAN)
8 4025 Remote Annunciator Expander (RAN-EX)
9 4035 Remote LED Driver (RLD)
10 4040 Remote LED Driver Expander (RLD-EX)
11 3000-6860 Remote Power Converter (RPC)1
12 2936 Ten Zone Class B (TZB)
13 2941 Five Zone Class A (FZA)
Detectors / Modules
14 55000-550 ISH-550 Ion Sensor Head
15 55000-650 PSH-650 Photoelectric Sensor Head
16 55000-450 TSH-450 Temperature Sensor Head
17 55000-750 IMB-750 Isolator Module
18 55000-830 MPM-830 Mini Priority Switch Monitor Module
19 55000-806 PMM-806 Priority Switch Monitor Module
20 55000-820 SMIO-820 Switch Monitor Input-Output Module
21 55000-825 SCM-825 Sounder Control Module
 
Notification Appliances
22 Other - NAC #1, 1.75 Amps Maximum
23 GMS24 - 15/75WR
24 GEC24 - 15/75WR
25 Other - NAC #2, 1.75 Amps Maximum
26 GMS24-15/75WR
27 GEC24-15/75WR
28 Other - NAC #3, 1.75 Amps Maximum
29 GMS24-15/75WR
30 GEC24-15/75WR
31 Other - NAC #4, 1.75 Amps Maximum
32 GMS24-15/75WR
33 GEC24-15/75WR
34 TOTAL STANDBY CURRENT - mA
35 TOTAL ALARM CURRENT - mA

Totals
A) Supervisory (standby) Current - mA (Item 34, above)
B) Supervisory Time in Hours (24 or 60)
C) Supervisory Requirements (A x B)
D) Power Supply Size (Enter .00575 or .0075) or Alarm Current (Item 35, above)
E) Alarm Time in Minutes (For 5mins enter .0833; for 10mins enter .167)
F) Alarm Requirement (D x E)
G) Battery Backup Requirement (C + F)
H) 20% Safety Factor (G x .2)
I) Battery Requirement w/ 20% Safety Factor (G + H)
J) Required Battery Size in Amps.

Notes:
1. Required for remote ACMs.
2. SLC Loops are Current Limited at 250mA in alarm. This requirement is included on the last line of     the Detectors/Modules section of this chart.
3. Review the top line for the indication of standby and alarm current.
4. Current values are in mAmps unless otherwise specified.

 