Standard Features
- Three year warranty
- UL listed (UL 864)
- CSFM listed
- Conform to NFPA 72
- Plug-in modular design for quick service
- 24 volt DC operation
- Supervised Class A or B initiating circuits
- Supervised Class A or B signaling circuits
- Supervised circuit/indicator for Waterflow alarm
- Supervised remote zone alarm & trouble annunciation
- Low or disconnected battery supervision
- Compatible with many two wire detectors
- Power output for four wire detectors
- Connection for reverse polarity remote station
- Zone trouble silence switch with ring back
- Zone disable switch/Zone lock-in reset
- Supplementary dry trouble contacts Form C
- Two sets of dry alarm contacts Form C
- Float charger for sealed batteries
- Alarm and trouble indication by zone
- LED diagnostic indicators
- Ground fault detection and indicator
- Eight point lightning and static protection
- 3 year limited warranty on all components
- Chemical releasing capability (with CZM module)
Specifications
AC Voltage: 120 VAC 60Hz
AC Current: 1.2 Amps
Battery Charger
Pulsed at 3 Hz (5% off, 95% on) duty cycle.
Voltage setting: 27.3 VDC
External Devices
Regulated 24 VDC, 2.4 Amps maximum, all loads.
Signal Circuit
Operation: Class A or B, reversing polarity.
Detection Circuits
Operation: Class A or B
Voltage, standby: 24 VDC regulated.
Current required to ensure alarm: 15 mA
Short circuit current: 35 mA +10/-2 mA.
Supervision current: 5 mA.
EOLR: 4.7K Ohms.
Maximum resistance per side: 50 Ohms.
Maximum total resistance: 100 Ohms.
Auxiliary Alarm Contacts
Dry supplementary alarm contacts on the CCA, two Form C, DPDT, rated at 5 Amps 28 VDC/120VAC resistive.
Auxiliary Trouble Contacts
One Form C (SPDT) contact set rated at 2 Amps 28 VDC/120VAC resistive; 300 milliamperes inductive.
All